三相四線系列
Three-Phase+Neutral Series
● 6~100A額定電流
● 適合各種使用三相四線電源的電子設備
● 對三相供電不平衡的供電情況亦可正常工作
● 良好的共/差模抑制特性
● 解決設備的傳導發射、EMT、EMI問題,提高設備的抗干擾能力
● 可按不同的插損、工作電流、電壓、結構尺寸和端接方式需求定制
● Current ratings from 6 to 100A
● Suitable for different kinds of three-phase four lines equipment
● To maintain performance generally for unbalance load
● Very high common and differential mode attenuation
● To handle Conductive Emission, EFT and other EMI problem, enhance the anti-jamming performance of electronic equipment
● Customization design for different Insertion Loss, Rated Current, Rated Voltage, Size and Terminal Format requirements.
技術規格Specification
額定電壓 Rated Voltage | 440VAC |
| |
工作頻率 Operating Frequency | 50/60Hz |
| |
最大漏電流 Max. Leakage Current | 見各型號 | 測試條件250V/50Hz Testing Condition 250V/50Hz | |
介質耐壓 Hipot Test Voltage | 線-線(L-L) 線—零(L—N) | 2250VDC 1450VDC | 1分鐘 1min |
線-地(L-E) | 2700VDC | ||
氣候等級 Climatic Classification | 25/085/21 | 遵循IEC68-1標準 Per IEC68-1 standard |
型號 Model | 額定電流 Rated current | 電路類型 Electrical Schematics | 最大漏電流 Max. Leakage | 外殼類型 Housing | 端接方式 Connections |
通用型 | |||||
Q110-6CL | 6A | Fig.1 | <2mA | Fig.1 | |
Q110-10CL | 10A | Fig.1 | <2mA | Fig.1 | |
Q110-16ES | 16A | Fig.1 | <2mA | Fig.2 | |
Q110-20ES | 20A | Fig.1 | <2mA | Fig.2 | |
Q110-30GS | 30A | Fig.1 | <2mA | Fig.3 | |
Q110-50FS | 50A | Fig.1 | <2mA | Fig.4 | |
高性能型 |
| ||||
Q310-50KS | 50A | Fig.2 | <10mA | Fig.5 | |
Q310-100KS | 100A | Fig.2 | <20mA | Fig.6 |
插入損耗Insertion Loss
遵循CISPR No.17/GB7343標準,插入損耗是在輸入/輸出均為50Ω的條件下的測量值。
—CM(共模) —DM(差模)
Per CISPR No.17/GB7343 standard, — denotes Common Mode Insertion Loss with 50/50Ω testing condition, and — denotes Differential Mode Insertion Loss with 50/50Ω testing condition.
電路原理Electrical Schematics
Fig.1 |
Fig.2 |
外形尺寸Mechanical Data
Fig.1 |
Fig.2 |
Fig.3 |
Fig.4 |
Fig.5 |
Fig.6 |